Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2008 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 06/02/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE PLANTS IN FRONT OF SERVICE EQUIPMENT 2. HAVE DOUBLE TAP LOAD SIDE OF SERVICE DISCONNECT 3. TIGHTEN NEUTRAL BOND SCREW IN SERVICE DISCONNECT 4. INSTALL BLANKS IN OPEN BREAKER SPACES IN PANE 5. NEED GFI PROTECTION FOR BATH RECEPTACLE 6. CLOSE OFF ALL OPEN WIRING 7. REPLACE PAINTED OVER DEVICES 8. REPLACE CRACKED DEVICE COVERS 9. GROUNDING TYPE RECEPTACLES NOT ALLOWED WITHOUT PROPER EQUIPMENT GROUND 10. HAVE SEVERAL LOOSE RECEPTACLES - PROPERLY SECURE 11. PROTECT OR REMOVE OPEN ROMEX WIRING TO RECEPTACLE IN BACK BOOTH 12. REMOVE UNUSED WIRING ALL WORK IS TO BE DONE BY QUALIFIED ELECTRICIAN |