Permit: T08EL00973

Parcel: 122173920

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
06/06/2008 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
06/02/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE PLANTS IN FRONT OF SERVICE EQUIPMENT
2. HAVE DOUBLE TAP LOAD SIDE OF SERVICE DISCONNECT
3. TIGHTEN NEUTRAL BOND SCREW IN SERVICE DISCONNECT
4. INSTALL BLANKS IN OPEN BREAKER SPACES IN PANE
5. NEED GFI PROTECTION FOR BATH RECEPTACLE
6. CLOSE OFF ALL OPEN WIRING
7. REPLACE PAINTED OVER DEVICES
8. REPLACE CRACKED DEVICE COVERS
9. GROUNDING TYPE RECEPTACLES NOT ALLOWED WITHOUT PROPER EQUIPMENT GROUND
10. HAVE SEVERAL LOOSE RECEPTACLES - PROPERLY SECURE
11. PROTECT OR REMOVE OPEN ROMEX WIRING TO RECEPTACLE IN BACK BOOTH
12. REMOVE UNUSED WIRING

ALL WORK IS TO BE DONE BY QUALIFIED ELECTRICIAN