Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED LETTER FROM LICENSED ELECTRICIAN STATING ALL CORRECTIONS MADE MEET CURRENT CODE AND SAFE TO OCCUPY 2) SMOKE DETECTOR/ALARM MISSING AT BEDROOMS AND HALL 3) COVER MISSING AT BREAKER PANEL 4) 1" CLEARANCE REQUIRED AT WATER HEATER B-VENT FROM COMBUSTIBLE 5) BUBBLE COVER REQUIRED AT EXTERIOR OUTLET 6) CHECK ALL ITEMS LISTED FROM PREVIOUS INSPECTION |
|
| 05/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND FAULT RECEPTACLES REQUIRED AT KIT. COUNTER 2. GROUND FAULT RECEPTACLES REQUIRED AT BATHROOM 3. UNGROUNDED ELECTRICAL SYSTEM, GROUNDED TYPE RECEPTS. INSTALLED THROUGHOUT 4. WALL RECETS WITHOUT FACE PLATES 5. AN ENCLOSED CARPORT WITH EXPOSED ROMEX, OPEN SPLICES NO INSULATION ON CEILING 1HR SEPARATION REQ'D BETWEEN UNITS NOT WIRED PER CODE, LOOKS TO HAVE OPEN SEWER CONNECTION IN SAME ROOM. CHECK VENTING AT LAUNDRY. 6. NO HOUSE ADDRESS 7. BROKEN MISSING INSULATION ON WIRE AT WEATHERHEAD 8. SUB-PANEL TO HAVE ISOLATED NEUTRAL, BUSS, 3GRD. BUSS SEPARATE NEUTRALS, GRDS 9. EXT. WIRING BROKEN FIXTURES, WIRES UNSECURED, OPEN SPLICE BOXES 10. THIS INSPECTION TO BE TURNED IN TO MY SUPRV. FOR FURTHER REVIEW |