Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/27/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE WHITE TAPE TO IDENTIFY NEUTRAL WIRE BETWEEN PANEL AND J-BOX 2. USE MYERS HUB OR WATERPROOF NUTS ON CONNECTORS AT TOP OF PANEL 3. NEED GROUND WIRE FROM PANEL TO JUNCTION BOX. IF INSULATED NEEDS TO BE COLOR CODED GREEN 4. WHEN CONNECTING COPPER TO ALUMINUM USE APPROVED CONDUCTORS SO ALUMINUM AND COPPER DON'T TOUCH. SPLIT BOLT WITH BRASS SPACER IS MOST COMMON. |
|
| 06/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO ENERGIZE 2) RECALL WHEN COMPLETE 3) BOND GAS AND WATER |