Permit: T08EL00905

Parcel: 120062100

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/17/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/11/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ROOF ACCESS, SECURE RISE WITH 1/4" LAG BOLTS MIN OR 1/4" BOLTS THRU ADOBE WALL W/WASHERS ON EA. SIDE
06/05/2008 ELECTRIC - SERVICE UPGRADE Denied PROVIDE ACCESS TO ROOF
05/28/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL GROUND RODS 2-AT 6' APART
2) SECURE RISER PROPERLY/PROPER MOUNTING OF EQUIPMENT
3) TERMINATE ALL WIRING TO BREAKERS LISTED
4) LABEL ADDRESS-METAL RAISED LETTERING
5) PROVIDE GAS WATER BONDS
6) LABEL ALL CIRCUITS
05/23/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE RISER PROPERLY
2) INSTALL GROUND ROD SYSTEM
3) TERMINATE ALL WIRING TO BREAKER
4) LABEL ADDRESS METAL RAISED LETTERING
5) LABEL ALL CIRCUITS
6) PROVIDE GAS/WATER BONDS