Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/11/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE ROOF ACCESS, SECURE RISE WITH 1/4" LAG BOLTS MIN OR 1/4" BOLTS THRU ADOBE WALL W/WASHERS ON EA. SIDE |
|
| 06/05/2008 | ELECTRIC - SERVICE UPGRADE | Denied | PROVIDE ACCESS TO ROOF | |
| 05/28/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL GROUND RODS 2-AT 6' APART 2) SECURE RISER PROPERLY/PROPER MOUNTING OF EQUIPMENT 3) TERMINATE ALL WIRING TO BREAKERS LISTED 4) LABEL ADDRESS-METAL RAISED LETTERING 5) PROVIDE GAS WATER BONDS 6) LABEL ALL CIRCUITS |
|
| 05/23/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE RISER PROPERLY 2) INSTALL GROUND ROD SYSTEM 3) TERMINATE ALL WIRING TO BREAKER 4) LABEL ADDRESS METAL RAISED LETTERING 5) LABEL ALL CIRCUITS 6) PROVIDE GAS/WATER BONDS |