Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00890
Inspection Description - ELECTRIC - FINAL
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OTHER ITEMS FINISHED MEET WITH PAT TO DISCUSS PERMITS & PLANS BASED ON WORKING CLEARANCES OF DISCONNECT AS PER PERMIT #T07CM03387 |
|
12/08/2008 | ELECTRIC - FINAL | Partial Approval | PAT TO CHECK ON WORKING CLEARANCE VIOLATIONS FROM TI W/MECHANICAL SERVICE YARD *RECEIVED LETTER OF TORQUE |
|
11/06/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED TO ANCHOR GEAR TO CONCRETE PAD 2) PLEASE PROVIDE LETTER OF TORQUE 3) NEED TO BOND ALL PIPING SYSTEMS 4) NEED TO EXTEND CONCRETE PAD 5) RECALL WHEN ALL WORK COMPLETE 6) LABEL ALL BREAKERS FOR LOAD SERVICE 7) RECEIVED CHECK #19261 FOR $150.00 FOR SATURDAY INSPECTION. INFORMED TEP ON SITE, OK TO ENERGIZE NEW SERVICE |
|
10/31/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY CONTRACTOR |