Permit: T08EL00855

Parcel: 137060460


Addresses:

409 W DAKOTA ST

Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
05/15/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE & PROTECT ROMEX IN LAUNDRY ROOM
2. PROVIDE SECONDARY GROUND ROD OR EXPOSE
3. PROVIDE GAS BOND
4. PROVIDE SEALED CONNECTORS JUNCTION WITH CONDUIT WEST WALL TO MID-WEST BOX
5. SEAL ALL EXTERIOR BOXES WEATHERED
6. SECURE ALL EXTERIOR CONDUIT PROPERLY
7. GFCI PROTECT KITCHEN OUTLETS
8. GFCI PROTECT BATH OUTLETS
9. PROVIDE PROOF OF PERMIT SE ADDITION
10. RELEASE MECHANISMS ON BEDROOM WINDOWS MUST OPERATE W/O SEPARATE TOOLS
11. PROTECT ROMEX ENTRY
12. PERMIT CARPORT WITH ELECTRICAL