Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/12/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CIRCUIT DIRECTORY TO BE AS PER 408.4 - NO GENERAL LABELING OR ABBREVIATIONS 2. CONTRACTOR TO BUILD PLATFORM BELOW SERVICE TO MEET HEIGHTH |
|
| 07/28/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. #1 NOT COMPLETED (7/22/08 INSP.) 2. LOCK BOX WOULD NOT OPEN |
|
| 07/22/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. DISCONNECT FOR UNIT IS NOT ACCESSIBLE 2. A PERMANENT METAL ADDRESS LABEL IS NEEDED 3. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANEL 4. NM SHEATHING TO ENTER 1/4" MINIMUM 5. PLANS DO NOT REFLECT NEW WIRING (HOOD, RANGE) 6. NEED ACCESS TO INSPECT ATTIC/CRAWL SPACE 7. HOUSE 2-WIRE SYSTEM - PANEL 3 WIRE 8. PANEL TO BE NO MORE THAN 1/4" BOX TO SURFACE |
|
| 07/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. COULD NOT OPEN LOCK BOX 2. HAVE OPEN BOX ON BACK OF UNIT 3. RECALL & PROVIDE ACCESS TO INTERIOR OF UNIT 4. NO INSPECTION DONE |