Permit: T08EL00803

Parcel: 113080780


Addresses:

1279 E GLENN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/15/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/12/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CIRCUIT DIRECTORY TO BE AS PER 408.4 - NO GENERAL LABELING OR ABBREVIATIONS
2. CONTRACTOR TO BUILD PLATFORM BELOW SERVICE TO MEET HEIGHTH
07/28/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1. #1 NOT COMPLETED (7/22/08 INSP.)
2. LOCK BOX WOULD NOT OPEN
07/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. DISCONNECT FOR UNIT IS NOT ACCESSIBLE
2. A PERMANENT METAL ADDRESS LABEL IS NEEDED
3. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANEL
4. NM SHEATHING TO ENTER 1/4" MINIMUM
5. PLANS DO NOT REFLECT NEW WIRING (HOOD, RANGE)
6. NEED ACCESS TO INSPECT ATTIC/CRAWL SPACE
7. HOUSE 2-WIRE SYSTEM - PANEL 3 WIRE
8. PANEL TO BE NO MORE THAN 1/4" BOX TO SURFACE
07/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1. COULD NOT OPEN LOCK BOX
2. HAVE OPEN BOX ON BACK OF UNIT
3. RECALL & PROVIDE ACCESS TO INTERIOR OF UNIT
4. NO INSPECTION DONE