Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00801
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2008 | ELECTRIC - FINAL | Approved | ||
06/03/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* RICH BURMAN UL 847-664-2554 PLANS FOR SERVICE AND TRANSFORMER TO BE APPROVED BY PLAN REVIEW. DRAWINGS LEFT ON SITE HAVE NOT BEEN APPROVED. |
|
06/02/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED APPROVED PLANS FOR INSPECTION SOMEONE HAS REMOVED THEM? |
|
05/29/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO INSPECTION AT THIS TIME R&R 887-7630 SERVICE TO BE LISTED BY NRTL AS SUITABLE FOR USE AS SERVICE EQUIPMENT AS REQUIRED BY NEC 230.66 YOU MAY HIRE U.L OR OTHER NRTL TO COME OUT AND DO A FIELD EVALUATION TO CERTIFY THIS EQUIPMENT AS SERVICE EQUIPMENT. AS OF NOW, IT IS LISTED ONLY AS ENCLOSED INDUSTRIAL CONTROL PANEL. |
|
05/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PREVIOUS ITEMS NOT ADDRESSED |
|
05/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NO PLANS ON SITE 2. SERVICE EQUIPMENT - TO BE LISTED PER NEC 230.66 NO INSPECTION AT THIS TIME |