Permit: T08EL00784

Parcel: 13728027B


Addresses:

901 W VIRGINIA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/24/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/22/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BEDROOM CARPORT ADDITION OK
2) MISSING COVER PLATES THROUGHOUT
3) REAR PORCH REMOVED
05/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROOF OF PERMITS FOR REAR ATTACHED PORCH ADDITIONS
2) PROVIDE PROOF OF PERMITS FOR CARPORT ENCLOSURE TO ROOM
3) NOTES 2 & 3
4) MISSING SMOKE DETECTORS REAR BEDROOM
05/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL CIRCUITS IN PANEL
2) CIRCUIT BREAKERS TO BE SAME TYPE AS MAIN DISCONNECT
3) 3 POLE 30 AMP BREAKER #12 WIRE
4) DBL LUGGED BREAKER (TWO CIRCUITS ON ONE BREAKER) ONE CIRCUIT PER BREAKER ALLOWED
5) PLUG HOLE IN BOTTOM OF PANEL
6) LOOSE RED WIRE IN SERVICE NOT CONNECTED
7) NEED WEATHER PROOF COVER FOR OUTLET BELOW SERVICE
8) NEED GFCI RECEPTS IN KIT.
9) SMOKE DETECTORS IN BEDROOMS AND 1 IN HALLWAY