Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL PANEL (BREAKERS) 2) DRIVE GROUND RODS, BOND GAS AND ELECTRIC 3) PANEL MAIN BREAKER REQUIRED 4) POINT OF ATTACHMENT MUST BE MINIMUM 18" ABOVE ROOF 5) LOAD CALCULATION NEEDED TO DETERMINE SIZE OF MAIN BREAKER 6) LARGER DIAMETER RISER MAY BE REQUIRED BY TEP |