Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RAUL @ 551-5000 1. NEED PROTECTIVE BUSHING ON ALL CONNECTORS NEC 300.4F 2. WIRE NUTS TO BE USED FOR NUMBER OF CONDUCTORS THEY ARE LISTED FOR - NEC 110.3B 3. IDENTIFY UPS DISCONNECT - NEC 110.22 4. GUTTER IS UNDERSIZED - NEC 366.58 5. REMOVE ALL PAINT UNDER LUG IN GUTTER - NEC 12 6. MISSING LOCKNUTS FOR EMT INTO DISCONNECT - NEC 358.42 7. INSTALL A SIGN AT SERVICE PER NEC 702.8 A & B 8. DOES INSTALLATION COMPLY WITH NEC 645.11? |