Permit: T08EL00765

Parcel: 12218274A


Addresses:

1160 N WINSTEL BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/09/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RAUL @ 551-5000

1. NEED PROTECTIVE BUSHING ON ALL CONNECTORS
NEC 300.4F
2. WIRE NUTS TO BE USED FOR NUMBER OF CONDUCTORS THEY ARE LISTED FOR - NEC 110.3B
3. IDENTIFY UPS DISCONNECT - NEC 110.22
4. GUTTER IS UNDERSIZED - NEC 366.58
5. REMOVE ALL PAINT UNDER LUG IN GUTTER - NEC 12
6. MISSING LOCKNUTS FOR EMT INTO DISCONNECT -
NEC 358.42
7. INSTALL A SIGN AT SERVICE PER NEC 702.8 A & B
8. DOES INSTALLATION COMPLY WITH NEC 645.11?