Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T08EL00688
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Not Applicable
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2008 | ELECTRIC - UNDERGROUND | Not Applicable | IVRS - Inspection :* | |
04/28/2008 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNCOVER AT MID PT. CONDUIT FOR DEPTH OF PIPE 2) USE SCHEDULE 80 PVC AT SERV. 3) HOME RUN DBL LUGGED INTO MAIN DISCONNECT 4) NEED LOAD CALC HOUSE IS ALL ELECTRIC 125 AMP CAPACITY |