Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00671
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/10/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED BY WARD OF CASCASE |
|
09/09/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* BREAKER TO FEED PANEL B TO BE 2 POLE 70 RATED 22K AIC PANEL A AIC RATING TO BE 22K |
|
07/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AIC RATING OF BREAKERS NOT PER PLAN. CALLS FOR 22K 2. NEUTRALS & GROUNDS TO BE SEPARATE 3. CANNOT HAVE MORE THAN ONE BRANCH CIRCUIT FEEDING A STRUCTURE - NEC 225 4. INSTALLATION NOT PER PLAN. PLAN SHOWS LOAD ON PANEL B TO BE 63 AMPS & FEEDING WITH 60 AMP BREAKER HAVE ADDED MORE LOAD TO THIS PANEL 5. LABEL BREAKER FOR PANEL B @ PANEL A 6. NEED ACCESS TO ROOF |
|
07/15/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED TO HAVE APPROVED PLANS ON SITE. WORK DOES NOT APPEAR TO BE PER PLANS THAT ARE ONSITE WORK IS NOT CODE COMPLIANT HAVE ELECTRICAL CONTRACTOR ON SITE FOR INSPECTION 2. RECALL WHEN READY |