Permit: T08EL00647

Parcel: 107111550

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/24/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/16/2008 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
05/06/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
CORRECTIONS TO NUMEROUS TO LIST - PARTIAL INSPECTION

UNIT #1
1. USE LISTED MAST BRACE AND SECURE INTO STRUCTURE
NEC 230.28
2. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.12B
3. NEUTRAL #6 & SMALLER TO BE WHITE ENTIRE LENGTH
NEC 200.6
4. GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH
NEC 250.119
5. BOND WATER & GAS PIPES - NEC 250.104
6. PROPERLY CONNECT GROUNDING ELECTRODE CONDUCTOR TO ACORN - NEC 110.3 B
7. PROVIDE INTERIOR & ATTIC ACCESS (LADDER)

SERVICE FOR #2, 3 AND 4
1. OVERHEAD CONDUCTORS TO HAVE PROPER CLEARANCE TO GRADE - NEC 225.18
2. MINIMUM 50 AMP BREAKER FOR MOBILE HOME FEEDER
NEC 550.10
3. FEEDER SUPPLYING #2, 3 AND 4 NEED AN EQUIPMENT GROUND - NEC 250.32 B1
4. REMOVE TEMPORARY EQUIPMENT FROM INSIDE PANEL
5. PROVIDE CALCULATION FOR 100 AMP FEEDING (3) 60 AMP SUB-PANELS TO #2, 3 AND 4 - SEE NEC 225.39
6. BOND METAL PIPING TO SERVICE - NEC 250.104

ALSO,
BACK FED MAIN BREAKERS TO HAVE HOLD DOWN DEVICE
NEC 408.36F

PARTIAL INSPECTION ONLY - CONTRACTOR TO BE ON SITE TO HAVE ALL UNITS OPEN & ACCESS TO ALL EQUIPMENT CHECK ABOVE CORRECTION FOR ALL UNITS - PROVIDE ACCURATE JOB DESCRIPTION TO THIS PERMIT.