Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/16/2008 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 05/06/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS TO NUMEROUS TO LIST - PARTIAL INSPECTION UNIT #1 1. USE LISTED MAST BRACE AND SECURE INTO STRUCTURE NEC 230.28 2. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.12B 3. NEUTRAL #6 & SMALLER TO BE WHITE ENTIRE LENGTH NEC 200.6 4. GROUND #6 & SMALLER TO BE GREEN ENTIRE LENGTH NEC 250.119 5. BOND WATER & GAS PIPES - NEC 250.104 6. PROPERLY CONNECT GROUNDING ELECTRODE CONDUCTOR TO ACORN - NEC 110.3 B 7. PROVIDE INTERIOR & ATTIC ACCESS (LADDER) SERVICE FOR #2, 3 AND 4 1. OVERHEAD CONDUCTORS TO HAVE PROPER CLEARANCE TO GRADE - NEC 225.18 2. MINIMUM 50 AMP BREAKER FOR MOBILE HOME FEEDER NEC 550.10 3. FEEDER SUPPLYING #2, 3 AND 4 NEED AN EQUIPMENT GROUND - NEC 250.32 B1 4. REMOVE TEMPORARY EQUIPMENT FROM INSIDE PANEL 5. PROVIDE CALCULATION FOR 100 AMP FEEDING (3) 60 AMP SUB-PANELS TO #2, 3 AND 4 - SEE NEC 225.39 6. BOND METAL PIPING TO SERVICE - NEC 250.104 ALSO, BACK FED MAIN BREAKERS TO HAVE HOLD DOWN DEVICE NEC 408.36F PARTIAL INSPECTION ONLY - CONTRACTOR TO BE ON SITE TO HAVE ALL UNITS OPEN & ACCESS TO ALL EQUIPMENT CHECK ABOVE CORRECTION FOR ALL UNITS - PROVIDE ACCURATE JOB DESCRIPTION TO THIS PERMIT. |