Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE RELOCATION
Permit Number - T08EL00596
Inspection Description - ELECTRIC - SERVICE RELOCATION
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2008 | ELECTRIC - SERVICE RELOCATION | Partial Approval | IVRS - Inspection :* | |
04/21/2008 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MARK "SERVICE DISCONNECT" 2. INSTALL MAIN BONDING JUMPER 3. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BAR 4. ARRANGE BONDING JUMPERS TO PREVENT PARALLEL NEUTRAL PATH 5. FINISH WIRING TO CABINET AND HAVE FUSES INSTALLED 6. CHECK TERMINATIONS TIGHT |