Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. TIGHTEN ALL SCREWS FOR CLAMPS 2. REMOVE ALL PAINT AT CONTACT POINTS FOR CONDUCTOR AND PIPE SURFACES TO CLAMPS 3. BURY CONDUCTOR DEEPER TO PREVENT DAMAGE/THEFT |
|
| 04/30/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE T08EL00571 |
|
| 04/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED TERMINAL - DO NOT USE EQUIPMENT AS A PATH 2. GROUNDING ELECTRODE TO BE AS PER 250.64(D) |