Permit: T08EL00556

Parcel: 99999999L

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00556

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
08/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ALL PREVIOUS INSPECTION ITEMS FROM 7/1/08
2) LUGS NOT LISTED FOR MULTIPLE WIRE TERMINATIONS
07/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT NOT LISTED
NOT LISTED FOR USE AS SERVICE EQUIPMENT
2. LUG IN METER NOT MARKED FOR 2 WIRE TERMINATION
3. BONDING JUMPERS NOT SIZED PROPERLY NEC 250.102
4. MAIN BONDING JUMPER NOT SIZED PROPERLY - NEC 250.28
5. PAY REINSPECTION FEE BEFORE NEXT INSPECTION
05/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ALL PREVIOUS INSPECTION ITEMS
2. HAVE 100% COMPLETE TO AVOID REFEE
3. RECALL WHEN READY
04/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT SEE SERVICE CONDUCTOR SIZE
2. EXPOSE 2ND GROUND ROD
3. BOND METER ENCLOSURE - NEC 250.92
4. BONDING JUMPERS NOT SIZED PROPERLY - NEC 250.102
5. MAIN BONDING JUMPER NOT SIZED PROPERLY - NEC 250.28
6. MARK SERVICE DISCONNECT - NEC 230.70
7. BOND SERVICE RISER - NEC 250.92
8. EQUIPMENT NOT LISTED AND NOT MARKED AS BEING SUITABLE FOR USE AS SERVICE EQUIPMENT - NEC 230.66