Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00556
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL PREVIOUS INSPECTION ITEMS FROM 7/1/08 2) LUGS NOT LISTED FOR MULTIPLE WIRE TERMINATIONS |
|
07/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT NOT LISTED NOT LISTED FOR USE AS SERVICE EQUIPMENT 2. LUG IN METER NOT MARKED FOR 2 WIRE TERMINATION 3. BONDING JUMPERS NOT SIZED PROPERLY NEC 250.102 4. MAIN BONDING JUMPER NOT SIZED PROPERLY - NEC 250.28 5. PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
05/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ALL PREVIOUS INSPECTION ITEMS 2. HAVE 100% COMPLETE TO AVOID REFEE 3. RECALL WHEN READY |
|
04/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT SEE SERVICE CONDUCTOR SIZE 2. EXPOSE 2ND GROUND ROD 3. BOND METER ENCLOSURE - NEC 250.92 4. BONDING JUMPERS NOT SIZED PROPERLY - NEC 250.102 5. MAIN BONDING JUMPER NOT SIZED PROPERLY - NEC 250.28 6. MARK SERVICE DISCONNECT - NEC 230.70 7. BOND SERVICE RISER - NEC 250.92 8. EQUIPMENT NOT LISTED AND NOT MARKED AS BEING SUITABLE FOR USE AS SERVICE EQUIPMENT - NEC 230.66 |