Permit: T08EL00555

Parcel: 99999999L

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00555

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
08/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LUG NOT LISTED FOR MULTIPLE TERMINATIONS
2) COMPLETE ITEM #1 FROM INSPECTION ON 7/1/08
07/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT NOT LISTED
NOT LISTED FOR USE AS SERVICE EQUIPMENT - NEC 230.66
2. INSTALL MAIN BONDING JUMPER AND SIZE PROPERLY
NEC 250.28 AND 250.24
3. PAY REINSPECTION FEE BEFORE NEXT INSPECTION
05/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETE ALL PREVIOUS INSPECTION ITEMS
2. HAVE 100% COMPLETE TO AVOID REFEE
3. RECALL WHEN READY
04/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE 2ND GROUND ROD
2. BOND METER ENCLOSURE NEC 250.92
3. BONDING JUMPERS NOT SIZED PROPERLY - NEC 250.102
4. MAIN BONDING JUMPER NOT SIZED PROPERLY - NEC 250.28
5. MARK SERVICE DISCONNECT - NEC 230.70
6. BOND SERVICE RISER - NEC 250.92
7. EQUIPMENT NOT LISTED AND NOT MARKED AS BEING SUITABLE FOR USE AS SERVICE EQUIPMENT - NEC 230.66