Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00555
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LUG NOT LISTED FOR MULTIPLE TERMINATIONS 2) COMPLETE ITEM #1 FROM INSPECTION ON 7/1/08 |
|
07/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT NOT LISTED NOT LISTED FOR USE AS SERVICE EQUIPMENT - NEC 230.66 2. INSTALL MAIN BONDING JUMPER AND SIZE PROPERLY NEC 250.28 AND 250.24 3. PAY REINSPECTION FEE BEFORE NEXT INSPECTION |
|
05/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETE ALL PREVIOUS INSPECTION ITEMS 2. HAVE 100% COMPLETE TO AVOID REFEE 3. RECALL WHEN READY |
|
04/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXPOSE 2ND GROUND ROD 2. BOND METER ENCLOSURE NEC 250.92 3. BONDING JUMPERS NOT SIZED PROPERLY - NEC 250.102 4. MAIN BONDING JUMPER NOT SIZED PROPERLY - NEC 250.28 5. MARK SERVICE DISCONNECT - NEC 230.70 6. BOND SERVICE RISER - NEC 250.92 7. EQUIPMENT NOT LISTED AND NOT MARKED AS BEING SUITABLE FOR USE AS SERVICE EQUIPMENT - NEC 230.66 |