Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00553
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOU STILL NEED A MAIN BONDING JUMPER TO BOND NEUTRAL TO GROUNDING ELECTRODE - 250 NEC |
|
04/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* BOND BUSHING TO BOND TO ENCLOSURE NOT NEUTRAL BUSS |
|
04/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - BOND BUSHING REQUIRED ON RISER CONDUIT - BOND SIZE PER 250.66 NEC - FUTURE PEDESTAL WILL BE REQUIRED TO BE UL APPROVED |
|
04/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EXPOSE 2ND GROUND ROD |