Permit: T08EL00552

Parcel: 99999999L


Addresses:

5048 E GRANT RD


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00552

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
07/30/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LUG NOT LISTED FOR 2 WIRE TERMINATION
2. COMPLETE ITEM #1 FROM INSPECTION ON 5/6/08
07/01/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CONDUCTORS NOT IDENTIFIED AT METER
2. ADDRESS MISSING/HAS BEEN PAINTED OVER NEEDS TO BE PERMANENT
3. FINISH PREVIOUS ITEM 1, 3, 4 FROM 5/6/08 INSP.
AND #3 FROM 4/18/08 INSP.
05/06/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. SERVICE EQUIPMENT TO BE LISTED AND IDENTIFIED AS SUITABLE FOR USE AS SERVICE EQUIPMENT, NEC 230.66
2. GROUNDED CONDUCTOR TO BOND TO SERVICE DISCONNECT ENCLOSURE - NEC 250.24C
3. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO GROUNDED CONDUCTOR OR VIA MAIN BONDING JUMPR - NEC 250.24
4. LUGS TO BE USED FOR SIZES/COMBINATION OF CONDUCTORS THEY ARE LISTED FOR - NEC 110.3B
5. PREVIOUS CORRECTIONS NOT COMPLETE - DO NOT CALL IN BEFORE ALL COMPLETE OR A REINSPECTION FEE MAY BE CHARGED.
04/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOND RISER & NIPPLE - 250.92
2. PREVENT OBJECTIONABLE CURRENT - 250.6
3. WHERE IS 2ND GROUND ROD?
4. UNCOVER UNDERGROUND TO INSPECT
5. PLEASE VERIFY LISTING OF EQUIPMENT