Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00552
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/30/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LUG NOT LISTED FOR 2 WIRE TERMINATION 2. COMPLETE ITEM #1 FROM INSPECTION ON 5/6/08 |
|
07/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CONDUCTORS NOT IDENTIFIED AT METER 2. ADDRESS MISSING/HAS BEEN PAINTED OVER NEEDS TO BE PERMANENT 3. FINISH PREVIOUS ITEM 1, 3, 4 FROM 5/6/08 INSP. AND #3 FROM 4/18/08 INSP. |
|
05/06/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION 1. SERVICE EQUIPMENT TO BE LISTED AND IDENTIFIED AS SUITABLE FOR USE AS SERVICE EQUIPMENT, NEC 230.66 2. GROUNDED CONDUCTOR TO BOND TO SERVICE DISCONNECT ENCLOSURE - NEC 250.24C 3. GROUNDING ELECTRODE CONDUCTOR TO CONNECT DIRECTLY TO GROUNDED CONDUCTOR OR VIA MAIN BONDING JUMPR - NEC 250.24 4. LUGS TO BE USED FOR SIZES/COMBINATION OF CONDUCTORS THEY ARE LISTED FOR - NEC 110.3B 5. PREVIOUS CORRECTIONS NOT COMPLETE - DO NOT CALL IN BEFORE ALL COMPLETE OR A REINSPECTION FEE MAY BE CHARGED. |
|
04/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOND RISER & NIPPLE - 250.92 2. PREVENT OBJECTIONABLE CURRENT - 250.6 3. WHERE IS 2ND GROUND ROD? 4. UNCOVER UNDERGROUND TO INSPECT 5. PLEASE VERIFY LISTING OF EQUIPMENT |