Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00510
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/11/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* STILL NEED TO COMPLETE CORRECTION #2 FROM PREVIOUS INSPECTION |
|
04/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LUG FOR GROUNDING ELECTRODE CONDUCTORS NOT LISTED FOR TWO CONDUCTORS. USE SEPARATE LUG OR CHANGE TO DOUBLE BARREL LUG - NEC 110.3B 2. IDENTIFY "SERVICE DISCONNECT" AS SUCH - NEC 230.72B |