Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
Permit Number - T08EL00500
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/31/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REPLACE ALL CRACKE DEVICES AND COVERS 2. NEED WORKING SMOKE DETECTORS IN BEDROOMS & HALLWAY 3. FURNACE IS BLOCKING DISCONNECT FROM OPENING 4. PROVIDE GFI PROTECTION FOR KITCHEN COUNTER RECEPTACLES |
|
03/28/2008 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE ACCESS INTO BLDG TO INSURE SAFE TO RELEASE POWER |