Permit: T08EL00458

Parcel: 133384120

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/05/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/21/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT SEE INTO METER SECTION
2. GROUND RODS TO BE MIN. 6' APART
3. BOND RISER & OFFSET NIPPLE PER NEC 250.92
4. PANEL DOOR TO OPEN 90 DEG.
5. NEED DETAILED PANEL DIRECTORY NEC 408.4
6. CANNOT VERIFY WATER BOND
7. GENERATOR TO BE SIZED FOR LOAD TO BE CARRIED -
NEC 702.5
8. NEUTRALS & GROUNDS TO BE SEPARATE @ PANEL
9. INSTALL BREAKERS LISTED FOR USE IN PANEL
10. ELECTRICIAN TO BE ON SITE TO OPEN GENERATOR