Permit: T08EL00444

Parcel: 133270110


Addresses:

8032 E ROSEWOOD ST


Inspection Status: Partial Approval

Inspection History: ELECTRIC - RECONNECT

Permit Number - T08EL00444

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Partial Approval

Date Description Inspector Results Comments
03/31/2008 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1) CONNECTION APPROVED TEMPORARILY
2) DO NOT OCCUPY UNTIL PERMITS OBTAINED FOR MODIFICATION OF FIRST FLOOR AT SOUTHEAST CORNER
03/27/2008 ELECTRIC - RECONNECT Denied 1) THIS INSPECTION IS THE 1ST TIME ALLOWED INSIDE HOUSE. RECEPTACLES ON BOTH SIDES OF KITCHEN SINK TO BE GFI TYPE
2) REMOVE OR CORRECT WIRING UNDER KIT SINK (OPEN SPLICED WIRING AND UNPROTECTED WIRING)
3) REMOVE IMPROPERLY INSTALLED WASHER HOOK UP OUTSIDE REAR PORCH AND ALSO ANY UNUSED PLUMBING IN BASEMENT
4) PORCH ROOF OVER EXCAVATED AREA INSTALLED INCORRECTLY, MUST BE PER CODE
5) WILL NEED VERIFICATION OF WALL IN THIS AREA WHERE SLIDING GLASS DOOR AND WINDOW INSTALLED, FOR SUPPORT REASONS
6) THIS ADDITION WAS INSTALLED WITHOUT PERMITS ACCORDING TO OUR RECORDS
7) PLEASE PROVIDE PLANS AND OBTAIN A PERMIT FOR THE ADDITION (MODIFICATION) THUR OUR OFFICE AT 201 N. STONE
03/24/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED LICENSED ELECTRICIAN TO CORRECT ALL HAZARDOUS WIRING IN HOUSE BEFORE POWER CAN BE OBTAINED
03/20/2008 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. FILL BLANK SPACE IN PANEL
2. ROMEX BELOW 7' MUST BE PROTECTED
3. INTERIOR ACCESS REQUIRED
4. PLANS AND PERMITS REQUIRED FOR ROOF ADDITION OVER BACKYARD RECESSED AREA, AS WELL AS ENTIRE RECESSED STRUCTURE