Permit: T08EL00440

Parcel: 131043090


Addresses:

4809 E 27TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/09/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/23/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL JUNCTION BOX AT SPLICE POINT TO HOUSE PANEL
2. CANNOT USE NEUTRAL CONDUCTOR AS EQUIPMENT GROUND. INSTALL GROUNDING CONDUCTOR.
3. CANNOT USE GREEN CONDUCTORS AS NEUTRALS OR HOTS
4. PROPERLY INSTALL 1" SEAL TIGHT TO TOP OF PANEL
5. USE RAIN TIGHT CONNECTORS AS EMT
6. STRIP EMT WITHIN 3' OF BELL BOX
7. INSTALL ALL SCREWS BELL BOX COVER
8. USE WIRE NUTS PER RATING. HAVE 2 #4 IN WIRE NUT
9. NEED PANEL DIRECTORY