Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* REMOVE RACEWAY FROM ELEVATOR SHAFT |
|
| 04/09/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ONLY WIRING ASSOCIATED WITH ELEVATOR EQUIPMENT TO BE IN HOIST WAY MACHINE ROOM, ETC. --- NEC 620.37 |