Permit: T08EL00437

Parcel: 107150340


Addresses:

523 E KELSO ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/21/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. SPLICE INSULATION TO BE EQUAL
2. GROUND BOLT TO BE MINIMUM #10
07/16/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
06/23/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/20/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXPOSE GROUND RODS
2. EMT STILL NOT STRAPPED
3. NEED INTERIOR ACCESS TO UNITS
4. BOND WIRE STILL FLOATING ACROSS ROOF - RUN ALONG AND SECURE TO STRUCTURE

REFEE IF NOT CORRECT NEXT INSPECTION
06/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS TO BE MINIMUM 6' APART
2. GROUNDING ELECTRODE CONDUCTOR TO PROPERLY ATTACH TO GROUND ROD ACORNS
3. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES
4. SERVICE RISER TO BE LOWERED SO SERVICE HAS PROPER FRONT CLEARANCE
5. BONDING CONDUCTOR TO BE PROPERLY SECURED TO STRUCTURE USING PROPER SIZE STRAPS/RAN NEXT & WORKMANLIKE
6. GROUND FEEDER J-BOX
7. RE-GROUND PHONE AND TV TO SERVICE
8. PROVIDE INTERIOR ACCESS