Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SPLICE INSULATION TO BE EQUAL 2. GROUND BOLT TO BE MINIMUM #10 |
|
| 07/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 06/23/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXPOSE GROUND RODS 2. EMT STILL NOT STRAPPED 3. NEED INTERIOR ACCESS TO UNITS 4. BOND WIRE STILL FLOATING ACROSS ROOF - RUN ALONG AND SECURE TO STRUCTURE REFEE IF NOT CORRECT NEXT INSPECTION |
|
| 06/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS TO BE MINIMUM 6' APART 2. GROUNDING ELECTRODE CONDUCTOR TO PROPERLY ATTACH TO GROUND ROD ACORNS 3. EMT TO BE SECURED WITHIN 36" OF ENCLOSURES 4. SERVICE RISER TO BE LOWERED SO SERVICE HAS PROPER FRONT CLEARANCE 5. BONDING CONDUCTOR TO BE PROPERLY SECURED TO STRUCTURE USING PROPER SIZE STRAPS/RAN NEXT & WORKMANLIKE 6. GROUND FEEDER J-BOX 7. RE-GROUND PHONE AND TV TO SERVICE 8. PROVIDE INTERIOR ACCESS |