Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/18/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. MAINTAIN WORKING CLEARANCES AT SUBPANEL 2. LABEL BREAKERS AT SUB-PANEL 3. PROTECT CABLES AT REAR OF SUB-PANEL AND FILL UNUSED PORTION OF OPENING WITH A NON-COMBUSTIBLE PRODUCT 4. REMOVE MAIN BONDING SCREW SUB-PANEL 5. SERVICE ENERGIZED WITHOUT CLEARANCE |