Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00419
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS NOT COMPLETED |
|
06/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DEAD FRONT COVER NOT FITTING PROPERLY TO BREAKERS HAVE GAPS 2. NUMBER BREAKERS 3. IDENTIFY FACTORY PANEL DIRECTORY 4. SHED SUB-PANEL HAS ISSUES - #6 & SMALLER NEUTRAL TO BE WHITE ENTIRE LENGTH, HOLD DOWN CLIP FOR MAIN, WRONG TYPE BREAKERS, OPEN HOLE, NEED PROPER GROUND BAR |
|
05/20/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
05/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CHECK FOR AFTER HOURS INSPECTION RECEIVED FOR $150 CHECK #16097 |