Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ROMEX CABLES TO BE INDIVIDUALLY CONNECTED WITH CONNECTORS TO PANEL. 2. GROUNDS & NEUTRALS TO BE SEPARATE @ PANEL INSTALL GROUND BAR 3. NEUTRALS TO TERMINATE 1 PER TERMINAL NO OTHER WIRES TO TERMINATE UNDER TERMINAL 4. NEED DETAILED PANEL SCHEDULE 5. WHY ARE CIRCUITS BEING DOUBLED UP. WILL BREAKERS BE OVERLOADED? SHOULD MORE CIRCUITS BE ADDED TO PANEL 6. PANELS NOT TO BE INSTALLED IN CLOTHES CLOSETS |