Permit: T08EL00410

Parcel: 130083860

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00410

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
03/14/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROMEX CABLES TO BE INDIVIDUALLY CONNECTED WITH CONNECTORS TO PANEL.
2. GROUNDS & NEUTRALS TO BE SEPARATE @ PANEL
INSTALL GROUND BAR
3. NEUTRALS TO TERMINATE 1 PER TERMINAL NO OTHER WIRES TO TERMINATE UNDER TERMINAL
4. NEED DETAILED PANEL SCHEDULE
5. WHY ARE CIRCUITS BEING DOUBLED UP. WILL BREAKERS BE OVERLOADED? SHOULD MORE CIRCUITS BE ADDED TO PANEL
6. PANELS NOT TO BE INSTALLED IN CLOTHES CLOSETS