Permit: T08EL00397

Parcel: 14042023D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/21/2008 ELECTRIC - FINAL Approved
04/18/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TEMP 1000 AMP, DISP. BOARD IN EAST WALL
03/21/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/20/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FEEDER CONDUCTORS NOT RATED FOR 1200 AMP
NEC 310 & NEC 240.4 C
2. NEED PLANS & INSPECTION FOR ALL EQUIPMENT FED BY THIS MDS DO NOT ENERGIZE BEFORE APPROVAL
3. PULL BOXES (2) TO MDS ARE UNDERSIZED - NEC 314.28

PARTIAL INSPECTION