Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00397
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2008 | ELECTRIC - FINAL | Approved | ||
04/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TEMP 1000 AMP, DISP. BOARD IN EAST WALL |
|
03/21/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
03/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FEEDER CONDUCTORS NOT RATED FOR 1200 AMP NEC 310 & NEC 240.4 C 2. NEED PLANS & INSPECTION FOR ALL EQUIPMENT FED BY THIS MDS DO NOT ENERGIZE BEFORE APPROVAL 3. PULL BOXES (2) TO MDS ARE UNDERSIZED - NEC 314.28 PARTIAL INSPECTION |