Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00373
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2008 | ELECTRIC - FINAL | Approved | ||
03/18/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/07/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL SMOKE DETECTORS IN BEDROOMS PER MANUFACTURES INSTRUCTIONS 2. INSTALL SMOKE DETECTOR OUTSIDE BEDROOM 3. KITCHEN COUNTER RECEPTACLES & BATHROOM RECEPT TO BE GFI PROTECTED 4. REMOVE UNPROTECTED ROMEX @ BACK PORCH FOR RECEPTACLE 5. HAVE WIRES HANGING ABOVE BACK DOOR 6. COOLER RECEPTACLES TO BE INSTALLED IN WEATHERPROOF BOX 7. OUTDOOR RECEPTACLES TO BE GFI WITH WEATHERPROOF COVERS 8. CHECK GROUNDING TYPE RECEPTACLES HAVE EQUIPMENT GROUND 9. THIS WRITE UP IS FOR BOTH UNITS 10. HAVE UNITS OPEN FOR REINSPECTION |