Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08EL00355

Parcel: 140441730


Addresses:

5581 E FARMRIDGE DR


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00355

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/06/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL SMOKE DETECTORS IN BEDROOMS PER MANUFACTURES INSTRUCTIONS
2. SMOKE DETECTORS OUTSIDE BEDROOMS NOT INSTALLED PROPERLY. NEED TO BE INSTALLED WITHIN 4" OF CEILING DOWN TO MAX. OF 12"