Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00353
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/19/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH #5 OF PREVIOUS INSPECTION 2. CANNOT PARALLEL GROUNDED CONDUCTORS SMALLER THAN 1/0 3. GROUNDED CONDUCTORS TO BE IDENTIFIED WHITE |
|
03/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL 2 GROUND RODS MIN. 6' APART 2. NEED DETAILED PANEL SCHEDULE 3. REIDENTIFY WHITE WIRE USED AS HOT 4. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL 5. NEED FULL SIZE NEUTRAL TO ADDED NEUTRAL BAR 6. PANEL NOT LISTED FOR USE OF SPLIT BREAKERS 7. MARK "SERVICE DISCONNECT" 8. INSTALL ALL SCREWS IN DEAD FRONT 9. CANNOT USE SHEETMETAL SCREW FOR GROUND ATTACHMENT 10. SERVICE ENERGIZED PRIOR TO APPROVAL |