Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T08EL00353

Parcel: 133324620


Addresses:

9210 E SIMON PL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T08EL00353

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/19/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/11/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH #5 OF PREVIOUS INSPECTION
2. CANNOT PARALLEL GROUNDED CONDUCTORS
SMALLER THAN 1/0
3. GROUNDED CONDUCTORS TO BE IDENTIFIED WHITE
03/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL 2 GROUND RODS MIN. 6' APART
2. NEED DETAILED PANEL SCHEDULE
3. REIDENTIFY WHITE WIRE USED AS HOT
4. SEAL OPENING IN BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL
5. NEED FULL SIZE NEUTRAL TO ADDED NEUTRAL BAR
6. PANEL NOT LISTED FOR USE OF SPLIT BREAKERS
7. MARK "SERVICE DISCONNECT"
8. INSTALL ALL SCREWS IN DEAD FRONT
9. CANNOT USE SHEETMETAL SCREW FOR GROUND ATTACHMENT
10. SERVICE ENERGIZED PRIOR TO APPROVAL