Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* LABEL MAIN PANEL BREAKER |
|
| 03/17/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAIN BACKFILLED BREAKER TO HAVE MANUFACTURES HOLD DOWN 408.36(F) 2. CORRECTLY LABEL BREAKER AT MAIN PANEL 3. NO ABBREVIATION FOR CIRCUIT LABELING 4. FINISH #4, #9 AND #11 OF PREVIOUS INSPECTION *PLUMBING IS A DIFFERENT TRADE INSPECTOR AND HAS TO BE CALLED IN SEPARATE |
|
| 03/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SEPARATE GROUNDS & NEUTRALS AT SUB-PANEL 2. A MAIN DISCONNECTING MEANS IS NEEDED AT 2ND STRUCTURE 3. INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURES INSTRUCTIONS 4. LABEL CIRCUITS AS PER 408.4 5. PROTECT NM CABLES FROM PHYSICAL DAMAGE 6. WATER HEATER TO HAVE DISCONNECTING MEANS 7. PLEASE VERIFY PERMIT FOR NEW WATER HEATER 8. PLEASE PROVIDE ACCESS TO RECEPTACLES TO INSPECT 9. RECEPTACLE COVER TO BE AS PER 406.8 10. USE CORRECT SIZE STRAPS 11. VERIFY CONDUCTOR SIZE FOR BREAKER AMPACITY |