Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/10/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PHONE AND TV GROUND TO CONNECT TO SERVICE OR SERVICE MAST OR G.E.C. NOT J-BOX 2) NEED PROPERLY SIZED AND INSTALLED BOND CLAMP FOR WATER BOND PIPE NOT FAUCET 3) REMOVE ALL PAINT UNDER LUG IN J-BOX, ALSO LUGS ARE NOT TO BE STACKED 4) STILL NEED TO SEE GAS BOND |