Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING. CANNOT USE EMT & MINERALLAC STRAP 2. BOND GAS PIPING ON HOUSE SIDE OF METER. EACH UNITS GAS PIPING TO BE BONDED TO THE UNITS SERVICE 3. GROUND RODS TO BE MIN. 6' APART 4. INSTALL ROOF JACKS 5. CONNECT SERVICE CONDUCTORS TO OVERHEAD POSITION IN METER SECTION. SEE INSTRUCTION IN METER SECTION 6. MAKE "SERVICE DISCONNECT" 7. NEED PANEL DIRECTORIES |
|
| 03/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - OBTAIN A SERVICE UPGRADE PERMIT FOR BOTH UNITS A & B RECALL INSP. NEW SERVICES INSTALLED |