Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/22/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/11/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LISTED MAST BRACING 2. GROUND CLAMPS TO BE LISTED FOR USE ON GROUND RODS AND LISTED FOR DIRECT BURY 3. REMOVE PAINT AT GROUND CLAMP CONNECTION TO WATER PIPING 4. NEED DETAILED PANEL SCHEDULE 5. USE PROPER FITTING FOR CONNECTION OF BELL BOX 6. ONE NEUTRAL PER TERMINAL NOT TO BE SHARED WITH ANY OTHER WIRES 7. USE PROPER FITTING FOR CONNECTION OF LB TO PANEL 8. SEAL OPENING WHERE WIRES ENTER BACK OF PANEL WITH NON-COMBUSTIBLE MATERIAL 9. USE WEATHER PROOF BOXES OUTDOORS 10. VERIFY IF POWER HAS BEEN OFF FOR MORE THAN 6 MONTHS WILL NEED RECONNECT INSPECTION 11. CANNOT SEE INTO METER SECTION |