Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/02/2008 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/19/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE INTERIOR & ROOF ACCESS 2. REMOVE OLD SERVICE 3. MIN #12CU FOR 20 AMP EQUIP. GROUND - NEC 250.122 4. CLEAN PAINTED OVER METER BUSSING - NEC 110 5. BRANCH CKT'S NOT TO RUN THROUGH COOLER BOX - NEC 312 6. MAKE SURE INTERIOR IS SAFE a. SMOKE DETECTOR EACH BEDROOM & HALL b. GFI PROTECT BATH & KITCHEN COUNTER RECEPTACLES c. NO OPEN/DAMAGED EQUIPMENT |