Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - FINAL | Approved | ||
| 09/12/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 03/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CIRCUIT LABELING TO BE PERMANENT 2. DRYWALL SCREWS NOT APPROVED HARDWARE 3. GAS BONDING TO BE TO INTERIOR SIDE PIPING 4. A BOND BUSHING IS NEEDED FOR DOUBLE REDUCING WASHERS 5. FILL UNUSED PORTION OF OPENING IN BACK OF PANEL WITH A NON-COMBUSTIBLE PRODUCT 6. WHERE IS GROUNDING EQUIPMENT CONDUCTOR WITH PVC RACEWAY 7. NEED TO SEE ANY SPLICE OR JUNCTION BOXES TO NEW CONDUCTORS 8. ADDRESS ON STRUCTURE NOT THE SAME AS PERMIT |