Permit: T08EL00269

Parcel: 10602282B


Addresses:

38 W PRINCE RD #58

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/14/2008 ELECTRIC - FINAL Approved
02/22/2008 ELECTRIC - FINAL Denied 1) THE CORD TO THE RV UNIT IS 10/3 30 AMP WIRE-NEEDS TO PLUG INTO A 30 AMP RECEPT
2) YOU HAVE A STANDARD GFI RECEPTACLE ON THE SIDE OF PEDESTAL FED BY A 30 AMP BREAKER THE GFI RECEPT IS GOOD FOR ONLY 20 AMPS
3) INSIDE PEDESTAL YOU HAVE A 50 AMP RECPT ON A 50 AMP BREAKER WHICH IS OK BUT CANNOT BE USED
40 ITEM #1 NEEDS TO BE CORRECTED