Permit: T08EL00266

Parcel: 104071590


Addresses:

1509 W CALLE SIGLO

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/25/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/05/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RAY @ 272-5506

PARTIAL INSPECTION - CONSIDER HIRING A QUALIFIED ELECTRICIAN

1. SERVICE CONDUCTORS NOT TO BE WITHIN 10' HORIZONTALLY FROM POOL EDGE OR ABOVE POOL.
2. PROVIDE A FLASHING FOR MAST
3. NEED A LISTED MAST BRACE - NOT EMT AND SECURE INTO TRUSS, NOT ROOF SHEATHING
4. STRAP MAST ABOVE SERVICE
5. RE-GROUND PHONE & TV
6. GROUND RODS TO BE MINIMUM 6' APART & DRIVEN FLUSH MOVE OVER TO DIRT & USE ACORNS
7. SECURE G.E.C TO STRUCTURE
8. PROTECT ROMEX INTO SERVICE
9. STRAP EMT WITHIN 36" OF ENCLOSURES
10. USE SQD BREAKERS ONLY
11. USE SEALING TYPE LOCKNUTS
12. INSTALL NEW WATER BOND CLAMP