Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/05/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RAY @ 272-5506 PARTIAL INSPECTION - CONSIDER HIRING A QUALIFIED ELECTRICIAN 1. SERVICE CONDUCTORS NOT TO BE WITHIN 10' HORIZONTALLY FROM POOL EDGE OR ABOVE POOL. 2. PROVIDE A FLASHING FOR MAST 3. NEED A LISTED MAST BRACE - NOT EMT AND SECURE INTO TRUSS, NOT ROOF SHEATHING 4. STRAP MAST ABOVE SERVICE 5. RE-GROUND PHONE & TV 6. GROUND RODS TO BE MINIMUM 6' APART & DRIVEN FLUSH MOVE OVER TO DIRT & USE ACORNS 7. SECURE G.E.C TO STRUCTURE 8. PROTECT ROMEX INTO SERVICE 9. STRAP EMT WITHIN 36" OF ENCLOSURES 10. USE SQD BREAKERS ONLY 11. USE SEALING TYPE LOCKNUTS 12. INSTALL NEW WATER BOND CLAMP |