Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00265
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BONDING JUMPERS FROM XFMR NOT SIZED PROPERLY TO BE #4 2. SEPARATE GROUNDS & NEUTRALS @ DISCONNECTS REMOVE MAIN BONDING JUMPERS 3. REMOVE MAIN BONDING JUMPER @ TRAILER PANEL 4. LABEL DISCONNECTS FOR LOAD SERVICES 5. MARK ON XFMR WHERE POWER COMES FROM 6. INSTALL FUSES IN DISCONNECTS |