Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/14/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND MAST NEC 250.92 2. BOND NIPPLE BETWEEN CT CABINET AND NEW DISCONNECT NEC 250.92 3. BRACE SERVICE CONDUCTORS PER INSTRUCTION IN CT CABINET 4. BOND WATER PIPING NEC 250.104 5. MARK "SERVICE DISCONNECTS" - NEC 230.70 6. OK GROUND RODS |