Permit: T08EL00256

Parcel: 113090750


Addresses:

2763 N PARK AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/06/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/29/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GAS BOND CLAMP LOOSE
2. PROVIDE NEW WATER BOND
3. PROPERLY GROUND TV & PHONE TO SERVICE
4. GROUND RODS TO BE MINIMUM 6' APART
5. BURY GROUNDING ELECTRODE CONDUCTOR
6. USE INSULATED TYPE CONNECTORS TO EXTEND WIRE
NOT TAPE
7. USE A SOLID #4CU TO BOND PIPES & THEN GO TO RODS
02/21/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ANSWER AT DOOR
2) NEED ACCESS ONTO PROPERTY FOR INSPECTION