Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/29/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GAS BOND CLAMP LOOSE 2. PROVIDE NEW WATER BOND 3. PROPERLY GROUND TV & PHONE TO SERVICE 4. GROUND RODS TO BE MINIMUM 6' APART 5. BURY GROUNDING ELECTRODE CONDUCTOR 6. USE INSULATED TYPE CONNECTORS TO EXTEND WIRE NOT TAPE 7. USE A SOLID #4CU TO BOND PIPES & THEN GO TO RODS |
|
| 02/21/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ANSWER AT DOOR 2) NEED ACCESS ONTO PROPERTY FOR INSPECTION |