Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/13/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE OPEN WIRING TO LIGHT FIXTURES ON BEAM @ BACK PORCH 2. INSTALL PLUGS IN OPENS @ BELL BOX CARPORT 3. SECURE RANGE RECEPTACLE TO WALL & INSTALL CONNECTOR WHERE CABLE ENTERS RECEPTACLE 4. KITCHEN COUNTER RECEPTACLES TO BE GFI PROTECTED 5. BATHROOM RECEPTACLES TO BE GFI PROTECTED THIS INCLUDES RECEPTACLE IN LIGHT FIXTURE 6. SMOKE DETECTORS TO BE MIN. 36" FROM AC VENTS 7. INSTALL PROPER DEAD FRONT ON PANEL - NO PLEXIGLASS |