Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00252
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2008 | ELECTRIC - FINAL | Approved | ||
02/27/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL RAY M. |
|
02/22/2008 | ELECTRIC - FINAL | Denied | 1) MAIN DISCONNECT AT SERVICE, CHANGE OUT LOADING ON LOAD SERVICE-REPLACE 2) DISCONNECT ALL UNUSED CONDUCTORS AND SERVICE 3) ID SERVICE AS 120/240 V 3 PHASE WITH HIGH LEG 4) PANEL A-PROPERLY SET #2 AC NEUTRAL ON PROPER LUG, REMOVE DBL LUGGING CIRCUIT AND TEMP WASHER (TIE OFF AND LABEL) 5) PANEL LPPA-REMOVE ANY MULTIPLE LUGGING TIE OFF AND LABEL 6) OLD GARAGE REMOVE WIRING 7) CORRECT AND RECALL 8) NOTICE: THIS SERVICE DATES BACK AT LEAST 50-60 YRS, IT IS IN AN OLD CONDITION STATUS-SUGGEST A POSSIBLE UPGRADE TO THIS BLDG |