Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00223
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SIGN NOT WIRED CORRECTLY - CORDS FOR PERMANENT WIRING, BOX TO BE OUTDOOR RATED 2. OUTDOOR LIGHT WIRING TO BE GROUNDED AND FOR OUTDOOR WIRING 3. GROUNDED RECEPTACLES ON AN UNGROUNDED SYSTEM 4. PROTECT BULB IN CLOSET - REMOVE OPEN WIRING 5. CORDS NOT FOR USE AS PERMANENT WIRING 6. MAINTAIN CLEARANCE IN FRONT OF PANEL 7. ROOF WIRING TO BE FOR OUTDOOR LOCATION 8. ELECTRICAL MAST NOT FOR SUPPORT OF OTHER WIRING 9. ONLY ONE NEUTRAL CONDUCTOR TO A LUG 10. NEED ANTIOXIDE COMPOUND FOR ALUMINUM WIRES 11. DO NOT SPLIT/FORK CONDUCTORS |