Permit: T08EL00222

Parcel: 121123710


Addresses:

1611 N BEVERLY AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/17/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/04/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE APPROVED BOX & FITTINGS FOR FLEX & MC/CABLE
2. WE HAVE EXPOSED CONDUCTORS FOR HOOD
3. BOXES IN COMBUSTIBLES 314.20
4. FINISH NM CABLES OUT TO PANEL
5. FINISH ITEMS #3, #4, #5
(THERE IS METALLIC WATER PIPING)

*UNIT APPEARS TO HAVE BEEN REMODELED -
WILL NOTIFY DNR
03/04/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. A PERMANENT METAL ADDRESS LABEL IS NEEDED
2. SUPPORT GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE
3. RISER HARDWARE TO BE 1/4" MINIMUM
4. A LISTED MAST BRACE KIT IS NEEDED
5. A GAS AND A WATER BOND ARE NEEDED
6. PLEASE VERIFY PERMITS OR ADD TO THIS PERMIT
FOR NEW WIRING/CIRCUITS IN ATTIC OPENING