Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/04/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED BOX & FITTINGS FOR FLEX & MC/CABLE 2. WE HAVE EXPOSED CONDUCTORS FOR HOOD 3. BOXES IN COMBUSTIBLES 314.20 4. FINISH NM CABLES OUT TO PANEL 5. FINISH ITEMS #3, #4, #5 (THERE IS METALLIC WATER PIPING) *UNIT APPEARS TO HAVE BEEN REMODELED - WILL NOTIFY DNR |
|
| 03/04/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. A PERMANENT METAL ADDRESS LABEL IS NEEDED 2. SUPPORT GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 3. RISER HARDWARE TO BE 1/4" MINIMUM 4. A LISTED MAST BRACE KIT IS NEEDED 5. A GAS AND A WATER BOND ARE NEEDED 6. PLEASE VERIFY PERMITS OR ADD TO THIS PERMIT FOR NEW WIRING/CIRCUITS IN ATTIC OPENING |