Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T08EL00220
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED DBL GROUND ROD AT SERVICE PANEL 6' APART 2) EXISTING WIRE ON SOUTH END OF HOUSE HAS BEEN CUT. REMOVE OR PUT IN ABOX (WHERE DOES IT TERMINATE ?) 3) BARE WIRES ON EXT. LIGHT AT REAR PORCH |
|
04/14/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ACCESS CODE GIVEN-NOT CORRECT 2) NEED TO VERIFY SMOKIES AND GFI RECEPTACLES ON ELECTRIC RECONNECT 2) NEED TO BOND GAS LINE |